AKRU-5A-30

General Electric Air AKRU-5A-30

IMAGES ARE FOR REFERENCE ONLY.

Select Product Condition:

View Specifications


AKRU-5A-30 Specifications

View Specifications

AKRU-5A-30, General Electric, AKR Series, type AKRU-30, fused 800A frame, accepts NEMA fuse class L fuses, 3PH, 3P, 600V, 100A-800A sensor rating available, 200kA@600V, Draw-Out, AKD-6, available either mechanically operated or electrically operated, with SST Solid State programmer, LSIG - Long-Time Short-Time Instantaneous and Ground Fault trip functions, low voltage power air circuit breakers

Manufacturer
General Electric
Subcategory
Air
Family
AKR Series
Amperage
800
Poles
3
Voltage
600

Electrical.com is NOT an authorized distributor for General Electric and therefore the manufacturer’s warranty does not apply. This product does include an Electrical.com 2 year warranty.

Pearl Logo
Standard Warranty Logo
Ships WorldWide Logo
Rush Shipping Logo
AKRU-5A-30 Specifications:
Part NumberAKRU-5A-30
Manufacturers
Sub-CategoryAir
TypeAKRU-30
Weight250 lbs
Amperage800
Poles3
Voltage600
FunctionsLSIG - Long-Time Short-Time Instantaneous and Ground Fault
ProtectionSolid State
ConnectionDraw-Out
Phase3
AIC Rating200kA@600V
The AKRU-5A-30 is a 3-pole low-voltage power air circuit breaker from General Electric' AKR Series, designed for industrial and commercial switchgear applications requiring high-current overcurrent protection and high fault-interrupting capability. Rated for an 800 A frame at 600, this integrally fused breaker combines a low-voltage air circuit breaker mechanism with current-limiting fuse protection for demanding power-distribution applications. Electrically, the AKRU-5A-30 uses a solid-state SST trip system capable of long-time, short-time, instantaneous, and ground-fault protection. These LSIG functions provide coordinated response to sustained overloads, short-duration fault conditions, severe short circuits, and qualifying ground faults. The breaker is designed to accept Class L current-limiting fuses and carries an interrupting capacity of , providing enhanced fault-current protection in properly rated low-voltage switchgear systems. Mechanically, the AKRU-5A-30 uses a draw-out construction for installation in compatible General Electric AKD-series switchgear. The draw-out design allows the breaker to be moved between connected, test, disconnected, and removed positions for inspection and maintenance without permanently disturbing the switchgear structure. Its 3-pole common-trip construction and integrally fused design make it suitable for main, feeder, and distribution applications requiring serviceability and high short-circuit withstand capability. Purchase the AKRU-5A-30 at Electrical.com, your reliable partner for industrial and commercial electrical products. Our selection includes trusted circuit breakers and power distribution components from manufacturers like Siemens, Eaton, Cutler-Hammer, and Schneider Electric, backed by a knowledgeable sales team ready to assist with technical questions, product selection, and support.